A & C SystemOffNormal

Supports SystemOffNormalAlarmType


Questions? Contact us
Generated: 21/11/2021 at 17:21:20 p.m.
A & C SystemOffNormal - 2 Test Cases
Test Case Id Test Type Keywords Test Case Description Test Requirements Expected Result

000

CTT Unavailable  Walk through the address space checking the type definition of OffNormalAlarmType type.
Step #
Action
Expected Result(s)

1

The type definition matches the UA Specifications (Part 9, Table 52), including the presense of the 'NormalState' property.

2

Walk through the address space looking for Instances of OffNormalAlarmType types and verify they comply to the type definition. Note: CTT Settings to specify where these instances are.

Instances are typed correctly.

001

CTT Unavailable  Invoke an event of each instance of OffNormalAlarmType alarm by writing to its corresponding trigger node and specifying a value that is considered NOT normal.
Step #
Action
Expected Result(s)

1

Each event type is received as expected. ServiceResult: Good; OperationResult: Good

2

repeat above with "next" value that's not normal, until all non-normal values have been specified.

ServiceResult: Good; OperationResult: Good

3

Acknowledge the event

ServiceResult: Good; OperationResult: Good

4

Confirm the event by calling the method on the Type.

ServiceResult: Good; OperationResult: Good

5

Clear the event state (no alarm) by reverting to a Normal value.

Verify the current state matches the NormalState property value. ServiceResult: Good; OperationResult: Good

6

Read the RETAIN bit

Retain bit is FALSE. ServiceResult: Good; OperationResult: Good